Cases

Boiler Feed Water Treatment Project for a Thermal Power Plant in China

Project Overview

The plant uses surface water to produce demineralized boiler make-up water. Clarification, filtration, ultrafiltration, BWRO, and EDI are combined to control suspended solids, dissolved salts, and residual ions.

KC-BW-FR8040 membrane elements are installed in the BWRO section to maintain stable permeate flow and high salt rejection under continuous power plant operation.

Treatment Process

1
Raw Surface Water
2
Coagulation and High-Rate Clarification
3
Rapid Gravity Filtration
4
Ultrafiltration
5
Cartridge Filtration
6
BWRO
7
EDI Polishing
8
Demineralized Water Tank
1
Raw Surface Water
2
Coagulation and High-Rate Clarification
3
Rapid Gravity Filtration
4
Ultrafiltration
5
Cartridge Filtration
6
BWRO
7
EDI Polishing
8
Demineralized Water Tank

RO System Parameters

The BWRO section includes two parallel trains, each using a 24:12 two-stage array with 6 KC-BW-FR8040 elements per pressure vessel. The system contains 216 elements per train and 432 elements in total.

The design flux is approximately 19.0 LMH, with a 75% recovery rate, an operating pressure of 0.8–1.1 MPa, and a system salt rejection of approximately 99.3%.

Each train produces approximately 153 m³/h of permeate. The combined design capacity is approximately 305 m³/h, equivalent to about 7,330 m³/day.